EATON Pulsar Series and Powerware Series Product Catalogue
Part Numbers 650 850 1150 1550 2000 RT2U
Tower 68 450 68 452 68 454 68 457 /
Rack1U 68 451 68 453 68 455 68 458 /
Convertible Tower/Rack / / / / 68 460
Full user interface:
- ON/OFF button for UPS and outlets
- Load protected/ not protected LED
- Utilised power level/Battery charge level
- Status of switchable outlets
Panel for batteries replacement
(Hot swappable)
1 USB port + 1 serial port +
remote ON/OFF
4 IEC 10A sockets,
including 2 programmable sockets
Communication card slot
TECHNICAL SPECIFICATIONS
650 850 1150 1550 2000
Rating (VA/W) 650 VA / 420 W 850 VA / 600 W 1150 VA / 770 W 1550 VA / 1100 W 2000 VA / 1600 W
Format Tower or 1U Rack Tower or 1U Rack Tower or 1U Rack Tower or 1U Rack RT2U (tower / rack 2U)
Electrical characteristics
Technology Line-Interactive High Frequency (Booster + Fader)
Input voltage and frequency ranges with-
out using batteries
160V-294V (adjustable to 150V-294V) 47 to 70 Hz (50 Hz system), 56.5 to 70 Hz (60 Hz system),
up to 40 Hz in low-sensitivity mode (programmable using Personal Solution-Pac software).
Output voltage and frequency 230 V (+6/-10 %) (Adjustable to 200 V (10 % derating of output power) / 208 V / 220 V / 230 V / 240 V), 50/60 Hz +/- 0.1 %
Connections
Input
1 IEC C14 (10 A) socket
Outputs
4 IEC C13 (10 A) 4 IEC C13 (10 A) 4 IEC C13 (10 A) 4 IEC C13 (10 A) 8 IEC C13 (10 A)
Remotely controlled sockets
2 groups of 1 x IEC C13
(10 A)
2 groups of 1 x IEC C13
(10 A)
2 groups of 1 x IEC C13
(10 A)
2 groups of 1 x IEC C13
(10 A)
2 groups of 2 x IEC C13
(10 A)
Additional outputs with HS MBP 4 FR/Schuko sockets or 3 BS sockets or 6 IEC 10 A sockets or terminal blocks (HW version)
Additional outputs with FlexPDU 8 FR/Schuko sockets or 6 BS sockets or 12 IEC 10 A sockets
Batteries
Typical backup times for 50 and 70% load 9/6 mn 16/7 mn 14/7 mn 14/7 mn 14/7 mn
Battery management Automatic weekly test (period adjustable), automatic recognition of external battery units => continuous maximisation
of backup time + deep discharge protection
Interfaces
Communication ports 1 USB port + 1 RS232 serial port and relay contacts (USB and RS232 ports cannot be used simultaneously)
+ 1 mini terminal block for remote ON/OFF and Remote Power Off
Communications card slots 1 slot for NMC Minislot card or NMC ModBus/JBus or MC Contacts/Serial
Operating conditions, standards and approvals
Operating temperature 0 to 35°C 0 to 35°C 0 to 35°C 0 to 40°C 0 to 40°C
Noise level < 40dbA < 40dbA < 40dbA < 40dbA < 45 dBA
Performance - Safety - EMC IEC/EN 62040-1-1 (Safety), IEC/EN 62040-2 EN 50091-2 class B (EMC), IEC/EN 62040-3 (Performance),
IEC/EN 61000-4-2, 61000-4-3, 61000-4-4; 61000-4-5, 61000-4-6, 61000-4-8 (EMI)
Approvals CE, CB report, TÜV
Dimensions W x D x H / Weight
Dimensions of the Tower 147 x 418 x 234 mm 147 x 418 x 234 mm 147 x 418 x 234 mm 147 x 492 x 234 mm 440 x 509 x 86.2 (2U) mm
Dimensions of the Rack 438 x 366 x 43.2 (1U) 438 x 512 x 43.2 (1U) 438 x 512 x 43.2 (1U) 438 x 556 x 43.2 (1U) 440 x 509 x 86.2 (2U)
Weight of the Tower/Rack 8.4/10.1 kg 10.85/16.1 kg 12.5/16.6 kg 16.53/20 kg 25.7 kg
Customer Service & Support
2 years warranty Standard product exchange, including the battery
Warranty+ Optional 3-years warranty (depending on the country please visit www.eaton.com/powerquality)
Eaton Evolution 1550 Tower
Eaton Evolution UPS